About Gas Generator Set Installation

Home > Service > FAQAbout Gas Generator Set Installation
About Gas Generator Set Installation 2017-12-23 09:39

Project Description

Description



Notice for installation of gas generator set:
 
1.Gas generator set’s room should be far away from open flame area.
 
2.Gas generator set’s room should be bright and spacious, require the installation of ventilator to ensure good ventilation.
 
3.When gas generator is installed, the base and foundation shall be in level. The shock pad is installed between the set and the base, and the contact area between the shock pad and the set is bigger than 60%.
 
4.Indoor should install lights switches, wiring, and electrical appliances should take explosion-proof measures, and be fixed firmly.
 
5.Gas generator set’s room should comply with fire requirements, be equipped with fire extinguishers and other fire appliances.
 
6. Gas generator set’s room should be installed combustible gas alarm device, so that combustible gas leakage can be found in time.
 
7.Below 60kW, single gas engine gas pipeline outside the main pipe diameter should be not less than 2 inches; the internal diameter of the part near the engine shall be not less than 1 inch. Gas generator sets over 60kW respectively are 3 inches and 2 inches. And the set must install gas valve (stainless steel ball valve), type drain valve, anti tempering device, When gas pipeline welding completed, clean up welding slag (with high-pressure air).
 
8.The gas must have desulfurization, dehydration, dedusting, the sulfur content ≤0.25nm³, hydrogen ≤ 10%.
 
9.The cooling water of the gas generator set must be soft water.